TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 9 A - 24 V DC coil
Main |
|
range of product |
TeSys Deca |
Product or component type |
Contactor |
Device short name |
LC1D |
contactor application |
Resistive load Motor control |
utilisation category |
AC-3 AC-1 AC-4 AC-3e |
Poles description |
3P |
[Ue] rated operational voltage |
Power circuit: <= 690 V AC 25...400 Hz Power circuit: <= 300 V DC |
[Ie] rated operational current |
9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit 25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit 9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit |
[Uc] control circuit voltage |
24 V DC |
Complementary |
|
Motor power kW |
2.2 kW at 220...230 V AC 50/60 Hz (AC-3) 4 kW at 380...400 V AC 50/60 Hz (AC-3) 4 kW at 415...440 V AC 50/60 Hz (AC-3) 5.5 kW at 500 V AC 50/60 Hz (AC-3) 5.5 kW at 660...690 V AC 50/60 Hz (AC-3) 2.2 kW at 400 V AC 50/60 Hz (AC-4) 2.2 kW at 220...230 V AC 50/60 Hz (AC-3e) 4 kW at 380...400 V AC 50/60 Hz (AC-3e) 4 kW at 415...440 V AC 50/60 Hz (AC-3e) 5.5 kW at 500 V AC 50/60 Hz (AC-3e) 5.5 kW at 660...690 V AC 50/60 Hz (AC-3e) |
Motor power hp |
1 hp at 230/240 V AC 50/60 Hz for 1 phase motors 2 hp at 200/208 V AC 50/60 Hz for 3 phases motors 2 hp at 230/240 V AC 50/60 Hz for 3 phases motors 5 hp at 460/480 V AC 50/60 Hz for 3 phases motors 7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors 0.33 hp at 115 V AC 50/60 Hz for 1 phase motors |
Compatibility code |
LC1D |
Pole contact composition |
3 NO |
Protective cover |
With |
[Ith] conventional free air thermal current |
25 A (at 60 °C) for power circuit 10 A (at 60 °C) for signalling circuit |
Irms rated making capacity |
250 A at 440 V for power circuit conforming to IEC 60947 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
Rated breaking capacity |
250 A at 440 V for power circuit conforming to IEC 60947 |
[Icw] rated short-time withstand current |
105 A 40 °C - 10 s for power circuit 210 A 40 °C - 1 s for power circuit 30 A 40 °C - 10 min for power circuit 61 A 40 °C - 1 min for power circuit 100 A - 1 s for signalling circuit 120 A - 500 ms for signalling circuit 140 A - 100 ms for signalling circuit |
Associated fuse rating |
10 A gG for signalling circuit conforming to IEC 60947-5-1 25 A gG at <= 690 V coordination type 1 for power circuit 20 A gG at <= 690 V coordination type 2 for power circuit |
Average impedance |
2.5 mOhm - Ith 25 A 50 Hz for power circuit |
Power dissipation per pole |
1.56 W AC-1 0.2 W AC-3 0.2 W AC-3e |
[Ui] rated insulation voltage |
Power circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified Signalling circuit: 600 V UL certified |
Overvoltage category |
III |
Pollution degree |
3 |
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947 |
Safety reliability level |
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
Mechanical durability |
30 Mcycles |
Electrical durability |
0.6 Mcycles 25 A AC-1 at Ue <= 440 V 2 Mcycles 9 A AC-3 at Ue <= 440 V 2 Mcycles 9 A AC-3e at Ue <= 440 V |
Control circuit type |
DC low consumption |
Coil technology |
Built-in bidirectional peak limiting diode suppressor |
Control circuit voltage limits |
0.1...0.3 Uc (-40…70 °C):drop-out DC 0.8...1.25 Uc (-40…60 °C):operational DC 1...1.25 Uc (60…70 °C):operational DC |
Inrush power in W |
2.4 W (at 20 °C) |
Hold-in power consumption in W |
2.4 W at 20 °C |
Operating time |
77 ±15 % ms closing 25 ±20 % ms opening |
Time constant |
40 ms |
Maximum operating rate |
3600 cyc/h 60 °C |
Connections - terminals |
Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end |
Tightening torque |
Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
Auxiliary contact composition |
1 NO + 1 NC |
Auxiliary contacts type |
Type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1 |
Signalling circuit frequency |
25...400 Hz |
Minimum switching voltage |
17 V for signalling circuit |
Minimum switching current |
5 mA for signalling circuit |
Insulation resistance |
> 10 MOhm for signalling circuit |
Non-overlap time |
1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact |
mounting support |
Plate Rail |
Environment |
|
Standards |
CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 IEC 60335-1 |
product certifications |
GL UL LROS (Lloyds register of shipping) CCC RINA BV GOST DNV CSA UKCA |
IP degree of protection |
IP20 front face conforming to IEC 60529 |
Protective treatment |
TH conforming to IEC 60068-2-30 |
Climatic withstand |
Conforming to IACS E10 exposure to damp heat conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
Permissible ambient air temperature around the device |
-40…60 °C 60…70 °C with derating |
Operating altitude |
0...3000 m |
Fire resistance |
850 °C conforming to IEC 60695-2-1 |
Flame retardance |
V1 conforming to UL 94 |
Mechanical robustness |
Vibrations contactor open (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz) Shocks contactor open (10 Gn for 11 ms) Shocks contactor closed (15 Gn for 11 ms) |
height |
77 mm |
Width |
45 mm |
Depth |
95 mm |
Net weight |
0.48 kg |
Packing Units |
|
Unit Type of Package 1 |
PCE |
Number of Units in Package 1 |
1 |
Package 1 Height |
5.000 cm |
Package 1 Width |
9.200 cm |
Package 1 Length |
11.200 cm |
Package 1 Weight |
528.000 g |
Unit Type of Package 2 |
S02 |
Number of Units in Package 2 |
15 |
Package 2 Height |
15.000 cm |
Package 2 Width |
30.000 cm |
Package 2 Length |
40.000 cm |
Package 2 Weight |
8.182 kg |
Unit Type of Package 3 |
P06 |
Number of Units in Package 3 |
240 |
Package 3 Height |
75.000 cm |
Package 3 Width |
60.000 cm |
Package 3 Length |
80.000 cm |
Package 3 Weight |
138.000 kg |
Contractual warranty |
|
Warranty |
18 months |